Document No: LT0255 F3200/NDU AS4428.1 Installation Manual
System Specifications
Issue 1.04 30 June 2004 Page 3-7
3.3.5.2 NDU Quiescent and Alarm Currents
Slimline NDU (FP0791/FP0792/FP0793/FP0794)
Operating Voltage : 24Vdc (18-28V)
Termination : For up to 2.5sqmm TPS
Quiescent
Alarm
Current Consumption : 25mA 80mA
Full cabinet NDU (FP0790)
Quiescent
Alarm
Current Consumption (Aust mode)
1
70mA 165mA
Current Consumption (NZ mode)
2
85mA 150mA
1. Includes controller, MAF/PSU, energised standby relay, PA0773 RS485 Bd, LCD
backlight off in quiescent state.
2. Includes controller, MAF/PSU, NZ Display Extender, energised standby and alarm
relays, PA0773 RS485 Bd. LCD backlight off in quiescent state.
3. Refer to Section 3.3.5.1 for additional module currents.
4. For FP0793 the I-Hub current needs to be added.