EasyManua.ls Logo

Tyco F3200 - Ancillary & Plant Isolate

Tyco F3200
142 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.DataSheet4U.com
Document No: LT0255 F3200/NDU AS4428.1 Installation Manual
Installation & Wiring
Issue 1.04 30 June 2004 Page 5-17
FIG 5.5.2
EXAMPLE OF MULTIPLE MINI-GENS WITH 3 BRANCHES OF SPEAKERS
Note that this configuration requires that the relay confirmation (ACT) be disabled.
FIG 5.5.3
EXAMPLE OF A SUPERVISED EVAC CCT USING 2 POLES OF AN 8RM RELAY
F3200
+
24V
Mini-
Gen
(PA0895)
-
+
-
+
-
S
+
-
+
-
S
+
-
FIRE PANEL
DC IN
DC IN
LINE
OUT
LINE
OUT
2-W LINK
FITTED
2-W LINK
FITTED
24V
Mini- Gen
(PA0895)
Bells +
Bells -
EOLR
10k 2W
EOLR
10k 2W
EOLR
10k 2W
+VBF
NO
Pole 2 NC
C
Pole 1 NO
NC
C
S
0V
4K7 EOLR
(27k for dual
branch)

Other manuals for Tyco F3200

Related product manuals