F3200/NDU AS4428.1 Installation Manual Document No: LT0255
Applications
Page 6-4 30 June 2004 Issue 1.04
CIRCUITS & ZONES (CONTINUED)
The option in Fig 6.1.3 A could be implemented by "tacking" the 560E resistor (or 6V8
Zener) onto the PCB. The 2 AZC option (Fig 6.1.4) could also be implemented by soldering
the extra resistor and wires onto the unused contact of the rotary switch on the PCB.
In all cases, "auto" is zone "normal".
OFF
┌──────────────o
AUTO ┌──┐
┌─────o─────o──────────────────────┤ +
╒╧╕ └──┘
6V8 ┌┴┐ ON o AZC
OR └┬┘ 2K7
560E └┬┘ ┌──┐
└──────┴────────┴─────────────────────────┤ -
└──┘
A. WITH A ROTARY SWITCH, "ON" IS B1 (INSTANT), "OFF" IS B2 (ALARM).
OFF
o
AUTO ┌──┐
┌────────────o─────o──────────────────────┤ +
┌┴┐ └──┘
2K7 ON o AZC
└┬┘
┌──┐
└───────────────┴─────────────────────────┤ -
└──┘
B. WITH A ROTARY SWITCH, "ON" IS B1 (INSTANT), "OFF" IS FAULT.
OFF
┌──────────────o
AUTO ┌──┐
──────o───┬──────────────────┤ +
╒╧╕ └──┘
6V8 ON o ┌┴┐ AZC
OR └┬┘ 2K7
560E └┬┘ ┌──┐
└───────────────┴──────┴──────────────────┤ -
└──┘
C. WITH A CENTRE-OFF TOGGLE SWITCH, "ON" IS B1 (INSTANT), "OFF" IS B2
(ALARM).
FIG 6.1.3
FAN CONTROL SWITCH WIRING WITH SINGLE AZC