Document:  LT0273    MX4428 MXP Engineering /Technical Manual 
 MXP Current Consumption 
Issue 1.5  24 March 2006  Page 5-3 
It is of interest to recalculate the current consumption assuming for example the supply 
voltage is only 17.0V (the minimum operating voltage of the MXP). In this case the 
consumption is increased to 721mA. It can be seen that if the responder loop power wiring 
has too much resistance, the voltage to the responders is reduced by their current 
consumption, which results in them requiring even more current and compounding the 
problem. 
 
5.1.2 QUIESCENT CURRENT 
The quiescent current of all responders can be calculated and used to ensure there is 
enough battery capacity and supply current at the MX4428. 
 
The quiescent current for the MX loop is calculated as in section 
3.2.2, but using the 
quiescent current instead of the alarm current. Then the MXP supply current can be 
calculated as described in section 
5.1. Once again iterative calculations may be required to 
adjust for the responder loop voltage drop. 
 
5.1.3 HEAT LOSS 
The heat loss from the MXP PCB can be calculated as follows – 
 
W = ITOT(mA) * 40V * ( 1 - PCE) / PCE  + IQ(mA) * 24V 
 
Where ..... 
  W  =  Heat loss in milliwatts 
 
  PCE  =  Power converter efficiency = 0.80 
 
  IQ  =   MXP quiescent current = 50mA at 24V. 
 
ITOT  =  Total current sourced into the AL and AR terminals, which can  
be calculated as shown in Section 
3.2.2 
 
Using the above figures, the equation simplifies to 
 
W(mW) = ITOT(mA) * 10V + 1200mW 
 
This can be calculated separately for quiescent and alarm conditions, depending on whether 
quiescent or alarm figures are used to calculate IQ. 
 
The maximum possible heat loss is 5.2 watts.