MX4428 MXP Engineering /Technical Manual  Document:  LT0273 
MXP Technical Description 
Page 7-10  24 March 2006   Issue 1.5 
In the event that there are isolator bases installed, but there is a short on the section of loop 
between the MXP and the first (or last) isolator, the MXP will detect the short and drive the 
loop only from the opposite end. Every 30 seconds it will very briefly try reconnecting the 
faulty end to see if the fault has gone away. This reconnection must be very brief (if the short 
is still present), as it will cause the loop voltage to collapse, and the voltage must be restored 
quickly enough so that the addressable devices retain enough charge in their power supply 
filter capacitors and do not reset. 
 
 
7.3   MXP ADJUSTMENTS  
None of these adjustments should require changing in the field, unless PCB components 
have been changed. 
 
7.3.1 40V ISO SUPPLY VOLTAGE ADJUSTMENT 
Disconnect all circuits from the analog loop terminals. Connect 24V to the responder loop 
power terminals. Adjust VR1 so that the voltage measured between TP16 “40V ISO” and 
TP15 “0V ISO” is 40.0V + / – 0.5V. 
 
7.3.2  TX DATA VOLTAGE ADJUSTMENT 
Disconnect all circuits from the analog loop terminals. Adjust VR2 so that the AC signal 
voltage measured with an oscilloscope between TP3 “LINE” and TP15 “0V ISO” is 4.0V - 
4.8V p-p. 
 
Refer to 
Figure 7.2 for an example waveform. Note that that waveform was captured with an 
analog loop and some addressable devices connected and so the measured voltage is 
slightly less than that specified. 
 
Note that the MXP will need to be connected to an MX4428 FIP, or standalone mode 
activated,  for any data to be transmitted. 
 
7.3.3  40V ISO SUPPLY CURRENT LIMIT ADJUSTMENT 
Disconnect all circuits from the analog loop terminals. Connect 24V to the responder loop 
power terminals. Apply a slowly increasing load current to the loop terminals and check at 
what current the overload circuit operates (i.e. current and voltage drop to zero before being 
restored by the software - this may happen repeatedly). The overload should occur at a 
current of 415mA to 430mA. If it is over this range snip out one of the resistors R22 - R25. If 
it is under this range, re-insert one of these resistors (R22 and R23 are 22Ω and R24 and 
R25 are 47Ω). Repeat the procedure as required.