27
Instruction for the installer
L1
L2
1,6 m -
18,4 m
20,0 m -
L 1
L 2
L max = L1+L2 = 20 m
FLUE CONFIGURATION Ø 60 mm
- curve with wide radius Ø 60 = 0,8 m
-
horizontal suction terminal Ø 60 = 1,2 m
-
horizontal evacuation terminal Ø 60 = 2,0 m
-
vertical evacuation duct Ø 80 + red. Ø 60 = 2,8 m
Note:
These values refer to flue systems mounted
with original UNICAL non flexible and smooth
pipes.
L max = L1+L2 =
2 Curve with wide radius
For each one of them deduct, from the maximum
allowed Length, the corresponding flue losses in meters.
Table of the flue losses for smoke accessories Ø 60 mm
The maximum allowable length of the horizontal separate pi-
pes Ø 60 is of 20 metres.
For rectilinear length it is intended without cur-
ves and suction/ evacuation terminals.
or the calculation related to the configurations, (example
1 or 2) it is necessary to deduct, from the maximum
allowed length, the resistance in meters related to the
different accessories (see table).