EasyManua.ls Logo

Unical EVE 05 CTFS 24 F - Calculating Pressure Losses in Ducts; Measuring Combustion Efficiency

Unical EVE 05 CTFS 24 F
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Installation info
fig. 22
fig. 21
135
45
C
2
1
250 min.
Example of check using wide radius
bends:
- 17 mt duct Ø 80 x 2 = 34 Pa
- 2x90° Ø 80 long radius bends 2x4 = 8 Pa
- horizontal Ø 80 air inlet terminal = 3 Pa
- horizontal Ø 80 terminal = 5 Pa
Tot. pressure loss = 50 Pa
1
2
A
Air
inlet
1
Smoke
outlet
B
2
Example N.2
CALCULATION OF PRESSURE LOSSES
FOR DISCHARGE AND SUCTION DUCTS
Bear in mind the following parameters when
calculating pressure losses:
- for each metre of duct with Ø 80 (both
suction and discharge) the pressure loss
is 2 Pa;
- for each 90° Ø 80 (R=D) bend with long
radius, the pressure loss is 4 Pa;
- for each 90° Ø 80 (R=½ D) bend with
short radius, the pressure loss is 14 Pa
- for the Ø 80 L = 0.5 m horizontal air inlet
terminal, the pressure loss is 3 Pa;
- for the Ø 80 L = 0.6 m horizontal
discharge end section, the pressure loss
is 5 Pa;
NB: These values refer to dis-
charges through original UNI-
CAL non-flexible and smooth
ducts.
Example N.2
Primary air suction from perimeter wall and
flue gas discharge from the same outside pe-
rimeter wall.
It is not allowed to position the 2 termi-
nals in opposite walls,
Maximum allowable pressure loss:
50 Pa
2.2.11- MEASUREMENTS OF
COMBUSTION EFFICIENCY
Ducts Ø 80 type B22 (C)
Coaxial ducts (A)
Dual ducts Ø 80 (B)
To determine combustion efficiency the fol-
lowing measurements must be made:
- the combustion air temperature measured
in hole 2 (see fig. 22).
- the flue gas temperature and CO
2
% mea-
sured in hole 1 (see fig. 22).
Make these measurements with the boi-
ler running in a steady state condition.
Air
inlet
Smoke
outlet
Analyser
probe
Analyser
probe
Analyser
probe
Analyser
probe

Related product manuals