Nominal power (1) kW 0,26 0,62
Maximum power input kW 1,25 0,83
Maximum current input A 2 1,45
Nominal air flow rate (1) m3/h 10847 13202
Internal heat
exchanger
Type of internal heat exchanger
Plate
N° internal heat exchangers
1 1
Water content L 1,7 2,1
Hydraulic
circuit
Useful head (1) kPa 86,5 74,7
Water content of hydronic circuit L 2,4 3,4
Maximum pressure hydronic kit (safety valve
bar 6 6
calibration)
Hydraulic connections inch 1"M 1"1/4 M
Minimum water capacity (8) L 110 110
Maximum circulator power kW 0,31 0,31
Max. circulator current input A 1,37 1,37
Circulator Energy Efficiency Index (EEI)
≤ 0,23 ≤ 0,23
Noise level Sound power level Lw (9) dB(A) 73 77
Electrical
data
Power supply
400V/3P+N+T/50Hz
Maximum power input kW 15 17,6
Maximum current input A 21,7 25,4
Maximum power input with antifreeze kit kW 15,2 17,8
Maximum current input with antifreeze kit A 22 25,8
Performance reffering to the following conditins, according to standards 14511:2018:
(1) Cooling: outdoor air temperature 35°C; in/out water temperature 12/7°C.
(2) Cooling: outdoor air temperature 35°C; in/out water temperature 23/18°C.
(3) Heating: outdoor air temperature temperatura aria esterna 7°C b.s. 6°C b.u.; in/out water temperature 30/35°C.
(4) Heating: outdoor air temperature 7°C b.s. 6°C b.u.; in/out water temperature 40/45°C.
(5) Cooling: in/out water temperature 7/12°C.
(6) Heating: medium cliatic conditions; Tbiv=-7°C; in/ out water temperature 30/35°C.
(7) Indicative data subject to changes. For the correct value, always refer to the technical label on the unit.
(8) Calculated for a decrease in system water temperature of 10°C with a defrost cycle lasting 6 minutes.
(9) Sound power: condition (3); value determined on the basis of measurements made in accordance with UNI EN ISO 9614-2, in compilance with
the requirements of Eurovent certification.
(*) activating the maximum Hz function
N.B. performance data are indicative and are subject to change. Furthermore, the output declared in points (1), (2), (3) and (4) refer to instan-
taneous power according to UNI EN 14511. The figure declared in points (5) and (6) is determined according to UNI EN 14825.
12.1 UNIT AND AUXILIARY ELECTRICAL DATA
On board controller circuit V/~/Hz 12/1/50
Remote controller circuit
NOTE: The electrical data are subject to change due to updates. It is therefore always necessary to refer to the technical specifications label
applied on the right side panel of the unit.
13. PRODUCT FICHE ACCORDING TO REGULATION (EU) No 811/2013
SCHEDA PRODOTTO – SERIE HP_OWER per applicazioni a bassa temperatura (Tout: 55°C)
Fornitore /
Supplier's name
Classe di efficienza energetica stagionale del riscaldamento d'ambiente
Seasonal space heating energy efficiency class
A+
A+
condizioni climatiche medie