17.4 AMBIENT AIR TEMPERATURE AND SUMMERISED TABLE
The units are designed and built to operate in summer mode, with condensation control, at outdoor air temperatures between -10°C and 48°C. I
heat pup mode, the allowed temperature range of the outdoor air is from -20°C to +35°C depending on the outlet water temperature as shown
in table below.
Operating limits
Water chiller mode
Room temperature
Minimum -15°C
Maximum 48°C
Water outlet temperature standard version
Minimum 5°C
Maximum 22°C
Water outlet temperature LV version
Minimum -8°C
Maximum 22°C
Heat pump mode
Room temperature
Minimum -20°C
Maximum 35°C
Outlet water temperature
Minimum 25°C
Maximum 60°C
Heat pump mode for domestic hot water
Room temperature with water at maximum 44°C
Minimum -20°C
Maximum40°C
Room temperature with water at maximum 60°C
Minimum-7°C
Maximum 26°C
Outlet water temperature
Minimum 25°C
Maximum 60°C
The following are the graphical operating limits for air-conditioning and domestic hot water production.
HEAT PUMP MODE
CHILLER MODE