8
1.8 - BOILER ANTIFREEZE PROTECTION (*)
(*) The frost protection is always active.
Even disabling the CH and DHW services
P
O
S
ANTIFREEZE FUNCTION
Power supplies 11 - SR (*) Status
function
antifreeze
Actions
Electric Gas
1
ON ON < 6 °C ON - Burner and Pump ON until T > 14°C
ON ON < 2 °C ON - Burner and Pump OFF until T > 5°C
- When T > 5°C then Burner and Pump
ON until T > 14°C.
2
ON OFF < 7 °C OFF - Pump ON until T > 10°C
OFF ON OFF - Burner and Pump OFF
OFF OFF OFF - Burner and Pump OFF
(*) Sensor 11 par. 2.2
ATTENTION (*) see general warn-
ings 1.1
The heating only models are NOT
suitable for the production of water
for human consumption according
to Ministerial Decree D.M. 174/2004.
ATTENTION!
ANY DAMAGE TO THE BOILER
CAUSED BY THE FORMATION OF
FOULING OR BY CORROSIVE WA-
TER WILL NOT BE COVERED BY
THE WARRANTY.
The treatment of the supply water
allows to prevent inconveniences
and maintain the functionality and
eciency of the generator over time.
The ideal water pH in heating systems
must be within:
To minimise corrosion, it is crucial to
use a corrosion inhibitor; in order for
it to work properly, the metal surfac-
es must be clean.
(see system protection ACCESSO-
RIES sect. in domestic price list)
VALUE MIN MAX
PH 6.5 8
Hardness [°fr] 9 15
This protection can intervene only if
the electricity and gas supplies are
connected.
If one of the two is not available and
upon reset 11 (SR) a temperature of < 2
°C is detected, the appliance will behave
as described in tab. pos 2.
The heating system can be protected
eectively from frost by using antifreeze
products with inhibitor for heating
systems (specic for multidmetal).
Do not use car engine antifreeze
products as they could damage the
water gaskets.