TSp Parameter
EASY
r
Desciption Min. Max.
P01
Enabled Services:
0:CH&DHWdisabled
1: CH enabled
2:DHWenabled
3:CH&DHWenabled
0 3
P02
Pump:Post-circulation
0: overrun 5 min.
1: continuous
0 1
P03
Outdoor minimum
temp °C
0 30
P04
Nightshift°C
0: T.A.
5÷30:Valuenightshift
0/5 30
P05
CH:Modulationmax
0 100
P06
Sweepermode
0: normal operation
1:100%liv.mod.max
2: 0% liv. mod. min
1 2
P07
Displaysthevaluecorrespon-
dingtothepositionofthe
heatingcontrolpanel,setpoint
oftheON-OFFrequest
0 1
P08
Access Code (#)
0 199
P09
bit 0 St: instantaneus, storage
tank
0 255
P10
IG-NAT:Modulationlevelat
start
0 100
To modify parameters is necessary password
TSp Parameter
EASY
r
Desciption Min. Max.
P11
IgL-GPL:Modulationlevelat
start
0 100
P12
FL-NAT:MinFanSpeed
60 40
P13
FLL-GPL:MinFanSpeed
10 40
P14
FH-NAT:MaxFanSpeed
41 70
P15
FHL-GPL:MaxFanSpeed
41 70
P16
HL:CH#1MinSetpoint
20 45
P17
HH-CH#1Max
Set point
50 85
P18
dL-MinACSSetpoint
25 45
P19
dH-MaxACSSetpoint
50 65
P20
FSt-Flamestabilizationtime
(after ignition)
0 30
P21
Tpe-Preventilationtime
0 5
P22
PL-PumpMinlevel
modulation
20 100
P23
Pr-Capacitytoowarteratio
50 100
P24
Pdt-PumpType
dt(°Cx2)
10
40
P25
Pt-Pumptype
0 = modulating
20÷100=pwmxafter
ignition
0/20
100
P26
Pv-ModulationSlope 1 50
P27
Hmf-FlowminCHmode
(l/h/10)
10 200
P28
BC-Boilermaxcapacity(kW) 10 100
P29
PMd-MaxPumpdelay 0 200
P30
Pld-LimitPumpdelay 0 200
P31
FHCH-NAT:FanspeedMax
CH mode
41 70
P32 FHCH-GPL:FanspeedMax
CH mode
41 70