(FA) Factory Parameters
ACTIVATION - SELECTION See section 1 (4.2)
Press the key (S) to access the FA parameters
unit. These parameters can be edited by enter-
ing the ACCESS CODE.
ACCESS CODE.
Press the key (B+) to enter the access code
Conrm with the key (D)
Once the access code has been entered, 1 or 2
Factory parameter units are displayed
2
UNIT 1 - FA PARAMETERS LIST
CODE RANGE DESCRIPTION
0 1
Type of Gas
0 = methane (default)
1 = GPL
0 100
Minimum pump modulation
level *
20 100
Maximum pump modulation
level
5 20
Pump temperature di󰀨er-
ential
0 6
Pump pause time during
CH / DHW service change
and vice-versa
0 = no pause
1÷6 = Time in seconds
UNIT 2 - FA PARAMETERS LIST
CODE RANGE DESCRIPTION
0 9
Boiler Power
10 70
Fan speed at start-up =
rpmx100
0 199
Minimum fan speed
(* 10+750) = rpmx100
0 199
Maximum fan speed
(* 10+5000) =r pmx100
1 20
Heating control: proportional
1 20
Heating control: integrative
1 20
Heating control: derivative
1 20
Domestic hot water control:
proportional
1 50
Domestic hot water control:
integrative
1 20
Domestic hot water control:
derivative
3 90
Ramp time CH
(Value *10) = sec
0 1
Function antilegionella
(storage tank boiler)
DISPLAY
Press the key (B+) to scroll the parameters.
3
1 4
1: Instantaneous boiler
2: Instantaneous boilers with
xed hysteresis
3: Heat. only boiler / or
storage tank (1 pump +
1 3-way val.)
4: Boiler with storage tank
2 pumps
0 1
Heat. pressure sensor
0 = absent / 1 = present
(default 0)
0 1
Unit:
0 = °C - bar 1 = °F - PSI
(default 0)
0 1
Mains frequency
0 = 50 Hz / 1 = 60 Hz
(default 0)
0 1
DHW and CH setpoint:
0 = bidirectional
1 = from remote control only
(default 0)
0 1
Primary Dt protection
0 = disabled
1 = enabled
(default 1)
0 100
Minimum output value
in CH and DHW (default 0)
(*) Do not set values below 20!