Specifications Sageon Micro Power Module Manual
PM990-4207-00, Rev 6
8-1
8. SPECIFICATIONS
Input AC
Voltage
Universal AC 85-300VAC (L-N. 1ph, or 3ph-Y, 3ph-delta [option].
Fully protected up to 440VAC (L-N)
Inrush Current
<9A RMS per rectifier
THD
Line Harmonics meet EN61000-3-2
Power Factor
>0.98 for >50% output power
Output DC
Voltage
-48VDC systems, adjustable range 42.0V to 59.5V
+24VDC systems, adjustable range 21.0V to 30.0V
Current Limit
Adjustable from 20 % to 120 % of rated output current
Power Limit
Varies by rectifier model. See the rectifier brochures for more information.
Efficiency
>90% at 100% output power for 48VDC systems
>88% at 100% output power for 24V systems
Regulation
+/- 1% or better over line, load and temperature
Noise
<1mV RMS Psophometrically weighted
<32dBrnC Voiceband
<10mV RMS and <100mV peak-to-peak (10kHz-100MHz)
Protection
Short Circuit
Can sustain short circuit at output terminals indefinitely
Reverse Battery Polarity
Internal fuse at output of RECTIFIER, integral battery circuit breakers and
detection/disconnection circuitry
High Voltage Shutdown
Rectifier shuts down if output exceeds programmed overvoltage limit
Electrostatic Discharge (ESD)
IEC 61000-4-2 (Level 4: Air 15kV, Contact 8kV)
AC Surge
IEC 61000-4-4 (EFT), Level 4
IEC 61000-4-5 (Impulse), Level X: 6kV/3kA
IEC 61000-4-12 (Ringwave), Level X: 6kV/500A
RF Immunity
IEC 61000-4-3 (Radiated), Level 4
IEC 61000-4-6 (Conducted), Level 3
RF Emissions
CISPR 22 Class B, (Conducted & Radiated)
Environmental
Operating
-40°C to +70°C
Full Power
-40°C to +55°C
Derated Operation
50% power at +70°C
Storage/Transport
-40°C to +70°C
Humidity
0 to 100% relative humidity, condensing
Acoustic Noise
< 60dB (A weighting)
Mechanical Dimensions
Width
483mm (19”)
Depth
355mm (14”)
Height*
88mm 352mm (3.4” 13.6”) *depending on configuration
Agency Compliances
Safety
IEC 60950, UL/CSA 60950
EMC
ETSI EN 300 386 V1.3.2 (2002-12)
Environmental
ETSI EN 300 019

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Unipower Sageon Micro Power Module and is the answer not in the manual?

Unipower Sageon Micro Power Module Specifications

Input Power IconInput Power
input voltage85-300VAC
inrush current<9A RMS per rectifier
power factor>0.98 for >50% output power
Output Power IconOutput Power
output voltage for -48VDC systemsadjustable range 42.0V to 59.5V
output voltage for +24VDC systemsadjustable range 21.0V to 30.0V
efficiency for 48VDC systems>90% at 100% output power
Environmental Conditions IconEnvironmental Conditions
operating temperature-40°C to +70°C
full power temperature range-40°C to +55°C
storage/transport temperature-40°C to +70°C
Mechanical Dimensions IconMechanical Dimensions
width483mm (19”)
depth355mm (14”)
height88mm – 352mm (3.4” – 13.6”) depending on configuration