Specifications Sageon Micro Power Module Manual
PM990-4207-00, Rev 6
8-1
8. SPECIFICATIONS
Input AC
Universal AC 85-300VAC (L-N. 1ph, or 3ph-Y, 3ph-delta [option].
Fully protected up to 440VAC (L-N)
Line Harmonics meet EN61000-3-2
>0.98 for >50% output power
Output DC
-48VDC systems, adjustable range 42.0V to 59.5V
+24VDC systems, adjustable range 21.0V to 30.0V
Adjustable from 20 % to 120 % of rated output current
Varies by rectifier model. See the rectifier brochures for more information.
>90% at 100% output power for 48VDC systems
>88% at 100% output power for 24V systems
+/- 1% or better over line, load and temperature
<1mV RMS Psophometrically weighted
<32dBrnC Voiceband
<10mV RMS and <100mV peak-to-peak (10kHz-100MHz)
Protection
Can sustain short circuit at output terminals indefinitely
Internal fuse at output of RECTIFIER, integral battery circuit breakers and
detection/disconnection circuitry
Rectifier shuts down if output exceeds programmed overvoltage limit
Electrostatic Discharge (ESD)
IEC 61000-4-2 (Level 4: Air 15kV, Contact 8kV)
IEC 61000-4-4 (EFT), Level 4
IEC 61000-4-5 (Impulse), Level X: 6kV/3kA
IEC 61000-4-12 (Ringwave), Level X: 6kV/500A
IEC 61000-4-3 (Radiated), Level 4
IEC 61000-4-6 (Conducted), Level 3
CISPR 22 Class B, (Conducted & Radiated)
Environmental
0 to 100% relative humidity, condensing
Mechanical Dimensions
88mm – 352mm (3.4” – 13.6”) *depending on configuration
Agency Compliances
ETSI EN 300 386 V1.3.2 (2002-12)