INSTALLATION (cont.)
G. Programming and Central Station Reporting
Thefollowingparameterscanbeconguredfromthedealerwebsite“Programming” Menu:
1. Automated and On Demand Test Signals (Default = Weekly)
The Automated Test signal interval can be changed from the dealer website
to monthly, weekly, or daily. In addition, an immediate test signal can be generated.
2. Activate/Deactivate Output Relay
Output relay #1 can be activated or deactivated from the dealer website.
This feature allows the installer to test the correct operation of this output
when it is connected to the alarm panel.
3. Normal State of Output Relay (Default = #1 Energized Closed)
The normal state of the Output Relay can be changed from the dealer website.
4. Output Relay 1 Mapping (Default = #1 Loss of Cellular Service)
There are 6 Trouble states that can be declared by the 4530, and each of
these states can be programmed from the dealer website to activate the
Output Relay.
The 6 Trouble states are:
•LowDCInputVoltage
•CableSupervisionTrouble(Panelto4530)
•LossofCellularService
•4530Disabled(viawebsitecommand)
•FailuretoreceiveACKfromCentralStation
•WatchdogCircuitTrouble
5. Send Trouble Condition to Central Station “Specic Event Reporting” (Default = Low DC
Input Voltage)
Any or all of the Trouble Conditions detectable the 4530 can be programmed to
report that condition (and its Restoral) to the monitoring Central Station.
(INSTALLATION continued next page)