4G PRIMARY
ALARM COMMUNICATOR
4
KEY FEATURES
A. FULL DATA Reporting. Compatible with most alarm panels using Contact ID (SIA
DC-05 Standard), SIA FSK Level 1 (SIA DC-03 Standard), Modem IIe/IIIa/IIIa
2
or
Pulse 4/2 digital dialer formats. All information sent by the alarm panel in these
formats (account number, zone information, User IDs, etc.) will be sent to the
central station using the GSM network.
B. Power Requirements: Requires constant 12V DC power from a power supply,
battery, or alarm panel with a constant 200 mA and a peak 600 mA for one second
during transmission.
C. Panel to 4530 Cable Supervision. Monitors continuity of the cable connecting the
panel’s telephone dialer to the 4530. This feature is activated through the website
www.uplink.com or by calling Uplink Customer Service:
1-888-9-UPLINK (1-888-987-5465)
D. Output. The 4530 has one programmable relay output. This output can be
programmed to activate upon the occurrence of one or more of the following
Trouble conditions:
•CellularNetworkLoss
•NoCentralStationAcknowledgement
•LowDCinputVoltage
•Panel/4530CableSupervisionTrouble
•UnitDisabledbyDealerCommand
•WatchdogCircuitActivation
E. Power Source Monitoring (Low DC Input Voltage Reporting). The 4530 can report a
low input Voltage condition to the central station when its DC input voltage drops
below 10.2V DC. It will report Low input Voltage Restoral at 11.4V DC.
F. Automated Testing. The 4530 can be programmed to send an automated test
signal to the central station on a monthly, weekly or daily interval.
(KEY FEATURES continued next page)