INSTALLATION (cont.)
D. Locating and Installing the 4530
The 4530 is housed in a plastic enclosure. The installer needs to supply DC power
from the panel via the AUX output, or battery, via a separate DC power source.
Input DC current is listed on page 23.
After carefully considering all of the issues outlined in Installations - General
Considerations, page 12, proceed as follows:
1. Separate the top and bottom of the enclosure by depressing the tab on
the bottom of the unit and then tilting the bottom of the plastic top
outward and up.
2. Connect the antenna that is supplied with the 4530. The Antenna
suppliedmaydifferfromtheonesdepictedintheguresinthismanual.
3. Go to the red, 4-position Dipswitch as shown in Figure 1 and set the
dipswitch as appropriate for this installation. (See DIP Switch Settings,
page 12.)
4. Place Dipswitch #4 (S4) in the ON position. The LEDs are now operating
in RSSI Mode. Locate a good mounting position based on a good
Received Signal Strength Indication (RSSI). It is recommended that the
installation location demonstrate an RSSI of at least -80 dBm (two solid green
LEDs). The minimum acceptable RSSI is -90 dBm (1 solid green LED).
(INSTALLATION continued next page)