Chapter 4: Commissioning
42 Stratos EX Hazardous Area Aspirating Smoke Detection System Installation Manual
Transport time verification
Maximum transport time verification test is the measure of the amount of time it
takes for the detector to respond to smoke that enters the pipe at the sampling
point furthest from the detector. The results of this test and the calculated
maximum transport time from PipeCAD must be recorded on the checklist.
Measured transport time less than the calculated time is acceptable.
To measure the maximum transport time of the system:
1. Determine the furthest sampling point from the detector.
2. Allow test smoke to enter pipe at the furthest sampling point.
3. Record the amount of time for the detector to respond. This is the actual
maximum transport time.
Gross smoke testing
The gross smoke test is a measurement of the amount of time elapsing from the
activation of the smoke generating medium, until PreAlarm and Fire 1 is reached.
This test should be repeated at least three times with consistent results.
Recommended smoke generating medium is aerosol-simulated smoke or wire
burner.
Aerosol smoke spray
There are a number of commercially available aerosol smoke sprays or “canned
smoke.” Please refer to your supplier for a recommended product. When using
canned smoke, introduce only enough smoke into the protected area that will
cause a Fire 1 condition. This may require a number of practice sprays. Follow
the manufacturer’s instructions.
Caution: Oil-based canisters that are used to test point detectors are not suitable
for testing aspirating systems, as the particulate is heavy and tends to drop out in
the pipe, never actually reaching the detector. Also, the oily residue that is left
behind may affect the functionality of the detector.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security AirSense Stratos EX and is the answer not in the manual?

UTC Fire and Security AirSense Stratos EX Specifications

General IconGeneral
BrandUTC Fire and Security
ModelAirSense Stratos EX
CategorySmoke Alarm
LanguageEnglish