EasyManua.ls Logo

UTC Fire and Security DET-TRONICS 95-8533 - User Manual

UTC Fire and Security DET-TRONICS 95-8533
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Instructions 95-8533
Eagle Quantum Premier
®
Fire and Gas Detection/Releasing System
7.1 9/09 95-8533

Table of Contents

Questions and Answers

  • G
    Gregory TapiaAug 13, 2025
    What to do if the Trouble Relay is active in UTC Fire and Security Controller?
    • K
      Karen GriffinAug 14, 2025
      If the Trouble Relay is active, it indicates that a monitored device in the system, including a ground fault, is in a fault condition. Use the front panel display/controls to view all points in alarm/fault and identify the faulted device. Then, repair or replace the faulted device as necessary.
  • A
    Anthony FergusonAug 17, 2025
    How to fix digital inputs that are not responding on UTC Fire and Security DET-TRONICS 95-8533?
    • D
      Deanna MedinaAug 17, 2025
      If digital inputs are not responding, here are a few things to check: - Ensure that P2 and P3 are fully inserted. - Use a voltmeter to measure input terminals with the contact closed to the input (it should measure 0 VDC when the input contact is closed, and approximately 23 VDC with the circuit open, with a 24 VDC input at the controller). - If the input does not respond to a contact closure, replace the module, verifying the response with EQ Safety System Software/textual display. - Also, verify the configuration, because the cause may be a configuration error or faulty wiring.
  • M
    Michele CoxAug 21, 2025
    What to do if relay outputs are not responding to an output command in UTC Fire and Security DET-TRONICS 95-8533 Controller?
    • E
      Erica GarciaAug 21, 2025
      If relay outputs are not responding to an output command, it could be due to a bad relay channel, faulty output wiring, or user logic issues. Check that P4 and P5 are fully inserted. When the output should be energized, measure contact resistance using an ohm meter. Verify that the wiring from the output is not open. Using EQ Safety System Software, verify that the logic is trying to operate the channel.
  • M
    Margaret MooreAug 25, 2025
    What to do if serial links are not responding in UTC Fire and Security Controller?
    • B
      Brian BishopAug 25, 2025
      If serial links are not responding, the issue could be faulty wiring, an incorrect serial link configuration, or the text display showing “Invalid Configuration”. Check that P8 and P9 are fully inserted. Verify that the communication LEDs are flashing. Ensure that the serial link configuration matches the host device. Verify that the wiring is not open or shorted.
  • J
    Jared Torres IIAug 28, 2025
    Why is the Controller Power LED/ Text Display OFF on my UTC Fire and Security DET-TRONICS 95-8533 Controller?
    • J
      Jaime GuzmanAug 29, 2025
      The Controller Power LED/Text Display might be off because there is no power to the input. Measure the input voltage (18 to 32 VDC). Check that P1 is fully inserted. If voltage is present and P1 is fully inserted, replace the controller.
  • J
    jamesmeltonSep 1, 2025
    Why is the LON Fault LED lit on UTC Fire and Security DET-TRONICS 95-8533?
    • W
      William KennedySep 1, 2025
      The LON Fault LED might be lit because the LON wiring is shorted or open. Check that P7 is fully inserted. Use the EQ Safety System Software to determine the location of the open or short via the LON Diagnostics screen. Use a multimeter to determine the wiring fault.
  • G
    Gary TurnerSep 4, 2025
    What to do if front panel pushbuttons are not working on UTC Fire and Security DET-TRONICS 95-8533 Controller?
    • S
      steven36Sep 5, 2025
      If the front panel pushbuttons are not working, verify that power is present and P1 is fully inserted. Cycle power to the controller.
  • T
    Tiffany GoldenSep 9, 2025
    What does it mean if the text display indicates a RTC Fault on UTC Fire and Security DET-TRONICS 95-8533?
    • K
      karensmithSep 9, 2025
      If the text display indicates an RTC Fault, it means there has been a power loss for more than 12 hours. Using the Safety System Software, execute “Set RTC” to download the current time into the Controller’s real-time clock. Alternatively, use the “Set Time and Date” menu in the Controller.

Summary

Instructions

Eagle Quantum Premier Fire and Gas Detection Releasing System

Overview of the Eagle Quantum Premier system for fire and gas detection and releasing.

Section 1 - Safety

Section 3 - Installation

Safety system Design Requirements

Discusses factors for designing an effective EQP system.

SAFETY SYSTEM DESIGN REQUIREMENTS

Outlines key factors for designing a proper EQP system.

IDENTIFYING THE AREA OF PROTECTION

Explains how to define the system's coverage area and identify hazard sources.

Identifying Wiring, Network (LON), and System Power Requirements

Covers requirements for wiring, network setup, and power for the system.

IDENTIFYING WIRING, NETWORK (LON), AND SYSTEM POWER REQUIREMENTS

Covers requirements for wiring, network setup, and power for the system.

Section 4 - Operation

Section 5 - Maintenance

LON COMMUNICATION HEARTBEAT

Controller based fault conditions

Field device based fault conditions

Lists fault conditions reported by field devices to the controller.

CONTROLLER LOGS

COMMUNICATION NETWORK FAULT OPERATION

Details how the system handles faults in the communication network, including isolation routines.

MULTIPLE WIRING FAULTS

Controller-to-Controller Communication (SLC485)

EQ21 xxPS Series Power Supplies and EQ2100 PSM Power Supply Monitor

EQ3730 EDIO Enhanced Discrete Input;Output Module

EQ3700 8 Channel DCIO Module

Describes the 8 Channel DCIO module's input/output configuration and supervision.

EQ3720 8 Channel Relay Module

EQ3710 AIM Analog Input Module

Explains the Analog Input Module's role in connecting 4-20 mA devices.

EQ3740 IPM Intelligent Protection Module

EQ25 xxARM Agent Release Module

Details the Agent Release Module's capability for agent release or deluge pre-action.

EQ25 xxSAM Signal Audible Module

EQ22 xxIDC Series Initiating Device Circuit (IDC)

EQ22 xxDCU and EQ22 xxDCUEX Digital Communication Units

Details the DCU's role in interfacing analog signals from detectors to the system.

Power Wiring

Determining Power Requirements

Table 3-2-Alarm Current Requirements at 24 vdc

EQ211 xPS, EQ213 xPS and EQ217 xPS Power Supplies

Backup Battery

Guides on calculating minimum backup battery size in Amp hours.

EQP2120 PS(-B) Power Supplies

Details specifications and usage of EQP2120PS(-B) power supplies.

Table 3-4-Backup Battery Requirements for Automatic Release of Extinguishing Systems Except Deluge

Shield Grounding

NETWORK AND NETWORK EXTENDER INSTALLATION

IMPORTANT!

INITIATING DEVICE CIRCUIT (IDC) INSTALLATION

Figure 3-5-Terminal Configuration for IDC

EQ22 xxIDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT

Describes the installation and configuration of the EQ22xxIDCGF Ground Fault Monitor.

WARNING!

EQ22 xxIDCSC series initiating Device Circuit Short Circuit

Describes the installation and configuration of the EQ22xxIDCSC Initiating Device Circuit.

EQ300 X CONTROLLER INSTALLATION

ENCLOSURE REQUIREMENTS

Specifies requirements for suitable enclosures based on location and ratings.

WIRING

Power Wiring

Details input voltage requirements and wire gauge considerations for the controller.

CONTROLLER TO CONTROLLER COMMUNICATION

Controller to Controller Communication (SLC485) with Signaling Line Circuit Classification Class A or B, per NFPA 72

Explains how to configure controllers for communication per NFPA 72 standards.

Connector P12, Terminals 66, 67 & 68, Port 4- RS-232 Modbus RTU Master;Slave (Non-Isolated)

EQ300 X REDUNDANT CONTROLLER INSTALLATION

Outlines installation requirements for redundant EQ300X controllers.

Wiring Connections for a Power Supply Monitor, EQ21 XXPS Series Power Supply and Backup Batteries

EQP2120 PS(-B) POWER SUPPLY AND REDUNDANCY MODULE INSTALLATION

ENHANCED DISCRETE INPUT;OUTPUT (EDIO) MODULE INSTALLATION

Connector P4, Terminals 13 to 24 Terminals A, B & C Channels 5 to 8 Input; Output Terminals

Supervised Input (IDC) Open Circuit Supervision

Details supervised input configuration for open circuit supervision.

Two-Wire Smoke Detectors

Supervised Output- Notification Supervised for Open & Short Circuits

Supervised Output- Agent Release (Solenoid Circuit)

Explains supervised output wiring for agent release circuits.

8 CHANNEL DISCRETE INPUT;OUTPUT (DCIO) MODULE INSTALLATION

NFPA - Class B, Style B Supervised Input (IDC) Open Circuit Supervision

Supervised Output for Automatic Release

Supervised Output for Deluge and Pre-action

Covers supervised output for deluge and pre-action systems.

8 CHANNEL RELAY MODULE INSTALLATION

Power Connector, Terminals 1 to 6 24 Vdc Power Input

ANALOG INPUT MODULE INSTALLATION

Channel Connectors - Terminals 1 to 24 4-20 mA Input Devices

Analog Input Module Channels used as NFPA 72 Approved 4-20 mA Flame Detector Input

Explains configuring AIM channels for NFPA 72 approved 4-20 mA flame detector input.

INTELLIGENT PROTECTION MODULE INSTALLATION

WIRING

Details electrical connections for the IPM.

Channels 1 to 3, Terminals 1 to 9 Channels 1 to 3 Inputs

Supervised Output Notification Supervised for Open & Short Circuits

Channels 7 and 8, Terminals 19 to 24 Supervised Output Agent Release

Explains supervised output wiring for agent release.

GAS DETECTOR LOCATION AND INSTALLATION

ENVIRONMENTS AND SUBSTANCES THAT AFFECT GAS DETECTOR PERFORMANCE

Discusses environmental factors and substances that impact gas detector performance.

EQ22 XXDCU DIGITAL COMMUNICATION UNIT USED WITH DET-TRONICS H2 S;O2 SENSORS OR OTHER TWO-WIRE 4-20 MA DEVICES

WARNING!

Warns against applying power with covers removed in potentially hazardous areas.

Sensor Separation for DCU with H2 S and O2 Sensors

EQ22 XXDCU DIGITAL COMMUNICATION UNIT USED WITH POINTWATCH;DUCTWATCH

EQ22 XXDCUEX DIGITAL COMMUNICATION UNIT (USED WITH DET-TRONICS COMBUSTIBLE GAS SENSORS)

Sensor Separation with DCUEX

Alternate Method

EQ25 XXARM AGENT RELEASE MODULE

Wiring

Provides instructions for wiring the ARM module.

Supervised Output for Deluge and Pre-action

EQ25 xxSAM SIGNAL AUDIBLE MODULE

SYSTEM CONFIGURATION

SETTING DEVICE NETWORK DEVICES

Details how to assign unique network addresses to devices.

CONTROLLER STATUS INDICATORS

Display Alarms Screen

DISPLAY ALARMS

SERIAL PORTS

REDUNDANCY INFO

Displays the current status of redundancy-related faults and controller health.

Lon Comm

CONTROLNET STATUS INDICATORS

SEQUENCE OF EVENTS DURING A CONFIGURATION DATA DOWNLOAD

Lists items affected during a configuration data download to the controller.

CONTROLLER REDUNDANCY

Power-up Sequence

Details the power-up sequence for a redundant controller pair.

Sequence of Events During a Configuration Download

Manual Switchover

Explains how to request a manual switchover between controllers.

Automatic Switchover

Describes the process of automatic switchover initiated by master controller errors.

ENHANCED DISCRETE I;O MODULE

8 CHANNEL DCIO MODULE

8 CHANNEL RELAY MODULE

ANALOG INPUT MODULE

INTELLIGENT PROTECTION MODULE

POWER-UP SEQUENCE

Details the IPM's power-up sequence and LED indications.

EMBEDDED LOGIC - PURPOSE

Explains the purpose of the IPM's embedded logic feature for local protection.

EMBEDDED LOGIC - CONTROL TRANSFER SEQUENCE DESCRIPTION

EMBEDDED LOGIC - OPERATION

EQ21 xxPSM POWER SUPPLY MONITOR

EQ2220 GFM GROUND FAULT MONITOR

Introduces the EQ2220GFM ground fault monitor and its LEDs.

EQ22 xxIDC SERIES INITIATING DEVICE CIRCUIT (IDC)

EQ22 xxDCU AND EQ22 xxDCUEX DIGITAL COMMUNICATION UNITS

Introduces the DCU and DCUEX units and their status LEDs.

EQ25 xxARM AGENT RELEASE MODULE

EQ25 xxSAM SIGNAL AUDIBLE MODULE

Details the EQ25xxSAM Signal Audible Module's operation and wiring.

SYSTEM STARTUP

PRE-OPERATION CHECKS

Lists essential checks to perform before powering up the system.

Ground Fault Monitor

GENERAL START-UP PROCEDURES

Provides general steps for starting up the system and programming it.

START-UP PROCEDURE FOR CONTROLLER

STARTUP PROCEDURE for EDIO MODULE

Details the startup procedure for the EDIO Module.

EDIO Startup

STARTUP PROCEDURE for DCIO MODULE

Details the startup procedure for the DCIO Module.

DCIO Startup

CALIBRATION AND ADJUSTMENTS

CALIBRATION ALGORITHM A FOR MANUAL CALIBRATION OF UNIVERSAL DCU

Provides a step-by-step guide for manually calibrating universal DCUs.

Sensor Replacement

CALIBRATION ALGORITHM C FOR COMBUSTIBLE GAS DCUS AND AUTOMATIC CALIBRATION OF UNIVERSAL DCUS

Provides calibration procedures for combustible gas DCUs and automatic calibration.

Initial Installation and Sensor Replacement - Combustible Gas (CGS Sensor)

Sensor Replacement - Toxic Gas

Outlines the procedure for replacing toxic gas sensors.

CALIBRATION ALGORITHM D FOR UNIVERSAL DCUS WITH O2 SENSOR

Sensor Replacement

Explains the procedure for replacing O2 sensors.

CALIBRATION ALGORITHM G FOR DCUS WITH POINTWATCH OR DUCTWATCH

TROUBLESHOOTING

REPLACEMENT PARTS

Controller Matrix

COMBUSTIBLE GAS SENSORS

LON TERMINATION MODULE

EQ3730 EDIO ENHANCED DISCRETE INPUT;OUTPUT MODULE

INPUT; INITIATING DEVICE CIRCUITS

OUTPUT; NOTIFICATION; RELEASING CIRCUITS

EQ3720 RELAY MODULE

Lists power requirements, input voltage, relay contacts, and communication specs for the Relay Module.

SUPERVISED OUTPUT RATING-Signaling Type, Class B, Style Y.

SUPERVISED OUTPUT RATING- Releasing Type

Provides the rating for supervised releasing output.

EQ3710 AIM ANALOG INPUT MODULE

EQ3740 IPM INTELLIGENT PROTECTION MODULE

SUPERVISED OUTPUT RATING-Signaling Type, Style Y - channel 6

SUPERVISED OUTPUT RATING- Releasing Type - CHANNEL 7 AND 8

Provides the rating for supervised releasing output on channels 7 and 8.

EQ21 XXPS POWER SUPPLIES

Details input voltage, current, output, power consumption, temperature, humidity, dimensions, and certification for EQ21XXPS.

EQP2120 PS(-B) POWER SUPPLIES

EQ22 xxIDC;IDCGF INITIATING DEVICE CIRCUIT

EQ2220 GFM GROUND FAULT MONITOR

EQ22 XXDCU AND EQ22 XXDCUEX DIGITAL COMMUNICATION UNIT

Details input voltage, power consumption, inputs, outputs, temperature, humidity, vibration, dimensions, and certification for DCU/DCUEX.

EQ24 xxNE NETWORK EXTENDER

COMBUSTIBLE GAS SENSOR

APPENDIX A - FM Approval Description

FIRE DETECTION & RELEASING

Covers FM verification of fire detection and releasing performance standards.

Table A-1-Circuit Classifications

Discrete I;O, Input (software configurable)

APPENDIX B - CSA INTERNATIONAL CERTIFICATION DESCRIPTION

GAS DETECTION

Details CSA verified performance for combustible and toxic gas detection.

Table D-1- List of Approved Equipment (Continued)

QUINT-DIODE;40 REDUNDANCY MODULE

ORDERING INFORMATION

Table D-2-Temperature and Humidity Ranges

Rocker Switch Table

UTC Fire and Security DET-TRONICS 95-8533 Specifications

General IconGeneral
BrandUTC Fire and Security
ModelDET-TRONICS 95-8533
CategoryController
ManufacturerUTC Fire and Security
Input Voltage24 VDC
Operating Temperature-40°C to +75°C
Housing MaterialAluminum
Protection RatingIP66