Remote Booster Power Supply Technical Reference Manual 5
Specifications
The following specifications apply to all BPS models.
AC line voltage
6.5 A BPS
10 A BPS
120 VAC / 230 VAC (50/60 Hz), 390 W
120 VAC / 230 VAC (50/60 Hz), 580 W
Sense voltage (input) 6 to 45 VDC (FWR and unfiltered DC)
Sense current (input) 6 mA at 24 VDC, 3 mA at 12 VDC, 12 mA at 45 VDC
NAC output voltage
(special application circuit)
19.1 to 26.40 VDC
Note: All NACs are supervised. Refer to the Remote Booster
Power Supply Compatibility List P/N 3100656 for the maximum
number of devices that can be used on a NAC circuit.
AUX output voltage
(special application circuit)
19.0 to 26.48 VDC
NAC/AUX output current 3.0 A max. per circuit with 0.35 power factor
(6.5 A or 10 A max. total for all NACs)
(6 A or 8 A max. total for all AUXs)
NAC/AUX capacitive loading 10,000 F max. for continuous NAC circuits
2,200 F max. for coded rate NAC circuits
2,200 F max. for AUX circuits
NAC/AUX class Class A or Class B
Wire size 18 to 12 AWG (0.75 to 2.5 mm
2
)
NAC EOL UL: 15 k (P/N EOL-15)
ULC: Use P/N EOL-P1 and select the 15 k resistor
Auxiliary output (continuous) 1 dedicated unsupervised, unswitched 200 mA auxiliary output
Voltage range: 19.49 to 26.85 VDC
Common trouble relay Form C, 1 A, 30 VDC (resistive)
Battery capacities 6.5 to 24 Ah for ECS/MNS/LSS applications
6.5 to 24 Ah for Security/Access Control applications
10 Ah maximum in BPS enclosure applications
Battery charger current limit [1] 1.2 A when the battery jumper wire is cut
2.1 A when the battery jumper wire is not cut
Operating environment
Operating temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Ground fault impedance 10 k
Intended installation
environment
Indoor-dry
[1] The battery charger is disabled automatically and will not charge the batteries when the unit is
activated via either of its sense inputs.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security Edwards BPS6A and is the answer not in the manual?

UTC Fire and Security Edwards BPS6A Specifications

General IconGeneral
BrandUTC Fire and Security
ModelEdwards BPS6A
CategoryPower Supply
LanguageEnglish

Related product manuals