Remote Booster Power Supply Technical Reference Manual 33
Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5) 200 mA AUX Continuous
(6) Sense 1 IN
(7) Sense 1 COM
(8) Sense 1OUT
(9) Sense 2 IN
(10) Sense 2 COM
(11) Sense 2 OUT
(12) Trouble NO
(13) Trouble COM
(14) Trouble NC
(15) Notification appliance circuit (NAC)
(16) UL listed EOL 15 k
(17) From existing fire alarm panel
notification circuit or CC1(S) module
(18) Out to EOL or next device
(19) NAC circuit
(20) UL listed EOL 15 k
(21) Data out to next device
(22) Data in from previous device or
Signature controller
(23) NAC circuit
(24) UL listed EOL 15 k
(25) EOL 15 k, when used as a NAC
(26) UL listed EOL relay
(27) EOL 47 k
Notes
When a booster power supply output is programmed as an AUX output, a listed EOL relay
(PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the AUX output.
When a booster power supply output is programmed as an NAC output, a 15 k EOL resistor
must be used for supervision.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security Edwards BPS6A and is the answer not in the manual?

UTC Fire and Security Edwards BPS6A Specifications

General IconGeneral
BrandUTC Fire and Security
ModelEdwards BPS6A
CategoryPower Supply
LanguageEnglish

Related product manuals