2 = Fault
Group 8, Autorestart parametersGroup 8, Autorestart parameters
Group 8, Autorestart parametersGroup 8, Autorestart parameters
Group 8, Autorestart parameters
Code Parameter Range Step Default Custom Description Page
8
..
..
. 1 Automatic restart: 0—10 1 0 0 = not in use 41
number of tries
8
. .
. .
. 2 Automatic restart: 1—6000 s 1 s 30 s 41
trial time
8
..
..
. 3 Automatic restart: 0—1 1 0 0 = Ramp 42
start function 1 = Flying start
8
..
..
. 4 Automatic restart of 0—1 1 0 0 = No 42
undervoltage 1 = Yes
8
..
..
. 5 Automatic restart of 0—1 1 0 0 = No 42
overvoltage 1 = Yes
8
..
..
. 6 Automatic restart of 0—1 1 0 0 = No 42
overcurrent 1 = Yes
8
. .
. .
. 7 Automatic restart of 0—1 1 0 0 = No 42
reference fault 1 = Yes
8
..
..
. 8 Automatic restart after 0—1 1 0 0 = No 42
over/undertemperature 1 = Yes
fault
Group 9, TGroup 9, T
Group 9, TGroup 9, T
Group 9, T
orque Controlorque Control
orque Controlorque Control
orque Control
Code Parameter Range Step Default Custom Description Page
9.1
Torque reference
selection
0—610
0 = None
1 = U
in
2 = I
in
3 = Panel Trq reference r2
4 = Ain1 (option board)
5 = Ain2 (option board)
6 = Fieldbus control
43
9.2
Torque reference
scaling bias
–100%--
+100%
1 0 0 = Not in use 43
9.3
Torque reference
scaling gain
–320%--
+320%
1 100 100 = No scaling 43
9.4 TC time constant 1—1000 ms 1 ms 15 ms 43
9.5
TC minimum control
limit
0—10.00 Hz
0.01
Hz
3.00 Hz 43