VV
VV
V
aconacon
aconacon
acon Page 7
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Vacon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Note!Note!
Note!Note!
Note! When joystick control is used, the direction control is generated from joystick
reference signal. See figure 5.4-1.
Analogue input scaling, parameters 2
..
..
. 16—2
. .
. .
. 19 are not used when joystick
control is used.
Fout
Uin
hystereesi +/-2% (+/-0,2 V)
+10V
-10V
Fmax
(par 1.2)
Fmin.
(par 1.1)
Fmin.
(par 1.1)
Fmax
(par 1.2)
Fout
Uin
Uin
+10V
-10V
Fmax
(par 1.2)
Fmax
(par 1.2)
If minimum frequency (par 1
..
..
. 1) >0, If minimum frequency (par 1
..
..
. 1) = 0,
hysteresis is ± 2% at reversing point. there is no hysteresis at reversing point.
Fig. 5-1 Joystick control Uin signal -10 V—+10 V.
88
88
8 Reference value is changed with digital input signals DIB5 and DIB6.
- switch in DIB5 closed = frequency reference increases
- switch in DIB6 closed = frequency reference decreases
Speed of reference change can be set with the parameter 2
..
..
. 20.
99
99
9 Same as setting 8 but the reference value is set to the minimum frequency
(par. 1
..
..
. 1) each time the frequency converter is stopped.
1010
1010
10 Same as setting 8 but the reference is stored to the memory over mains break.
When the value of the parameter 1
..
..
. 5 is set to 8, 9 or 10, the values of the
parameters 2
..
..
. 4 and 2
. .
. .
. 5 are automatically set to 11.
11
11
1
11
11
1 The minor of signals Uin and Iin is the frequency reference
1212
1212
12 The greater of signals Uin and Iin is the frequency reference
1313
1313
13 Panel reference r1 is the frequency reference
1414
1414
14 Maximum reference selection (recommended only at torque control)
1515
1515
15 U
in
/I
in
digital selection (see par. 2.3)
1. 61. 6
1. 61. 6
1. 6
Jogging speed referenceJogging speed reference
Jogging speed referenceJogging speed reference
Jogging speed reference
Parameter value defines the jogging speed selected with the digital input
1. 71. 7
1. 71. 7
1. 7
Current limitCurrent limit
Current limitCurrent limit
Current limit
This parameter determines the maximum motor current from the freqeuency
converter. To avoid motor overload, set this parameter according to the rated current
of the motor.
1. 81. 8
1. 81. 8
1. 8
U/f ratio selectionU/f ratio selection
U/f ratio selectionU/f ratio selection
U/f ratio selection
Linear: The voltage of the motor changes linearly with the frequency in the
00
00
0 constant flux area from 0 Hz to the field weakening point (par. 6
..
..
. 3)
where the nominal voltage is also supplied to the motor. See figure
5-2. Linear U/f ratio should be used in constant torque applications.