EasyManuals Logo

Vacon CX Manual

Vacon CX
70 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
Vacon Plc Phone: +358-201 2121 Fax:+358-201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
E-mail: application.team@vacon.com
Vacon Page 9
Pump control with autochange
1. 10 Nominal voltage of the motor
Find this value U
n
on the rating plate of the motor.
This parameter sets the Voltage at the field weakening point, parameter 6. 4, to
100% x U
n
motor
.
1. 11 Nominal frequency of the motor
Find this value f
n
on the rating plate of the motor.
This parameter sets the field weakening point, parameter 6. 3, to the
same value.
1. 12 Nominal speed of the motor
Find this value n
n
on the rating plate of the motor.
1. 13 Nominal current of the motor
Find this value I
n
on the rating plate of the motor.
1. 14 Supply voltage
Set parameter value according to the nominal voltage of the supply.
Values are pre-defined for CX/CXL2, CX/CXL/CXS4, CX/CXL/CXS5 and CX6
ranges, see table 6.4-1.
1. 15 Parameter conceal
Defines which parameter groups are available:
0 = All parameter groups are visible
1 = Only group 1 is visible
1. 16 Parameter value lock
Defines access to the changes of the parameter values:
0 = Parameter value changes enabled
1 = Parameter value changes disabled

Other manuals for Vacon CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon CX and is the answer not in the manual?

Vacon CX Specifications

General IconGeneral
BrandVacon
ModelCX
CategoryMedia Converter
LanguageEnglish

Related product manuals