EasyManuals Logo

Vaillant ecoFIT pure Series User Manual

Vaillant ecoFIT pure Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
36 Installation and maintenance instructions ecoFIT pure 0020230533_06
Clearance for the ignition electrodes: 3.5 to 4.5 mm
6. Make sure that the seal (5) is free from damage.
If necessary, replace the seal.
12.10 Cleaning the condensate trap
C
2
3
1
A
B
1. Unclip the lower section of the condensate trap (1) from
the upper section of the condensate trap (2).
2. Remove the float (3).
3. Flush out the float and lower section of the condensate
trap with water.
4. Fill the lower section of the condensate trap with water
up to 10 mm below the upper edge of the condensate
discharge pipe.
5. Re-insert the float (3).
Note
Check whether the float is present in the
condensate trap.
6. Clip the lower section of the condensate trap (1) into the
upper section of the condensate trap (2).
12.11 Installing the gas-air mixture unit
1. Install the burner.
2. Install two new burner seals in the burner hood.
3. Install the gas-air mixture unit.
4. Tighten the screws in a cross-wise pattern until the
burner flange fits closely and uniformly onto the mat-
ing surfaces.
Tightening torque: 7 Nm, if a torque spanner is
available
5. Install the flue pipe.
6. Install the air intake pipe.
12.12 Draining the product
1. Close the service valves of the product.
2. Start check programme P.05.
Overview of the check programmes ( Page 26)
3. Open the drain valves.
12.13 Checking the pre-charge pressure of the
expansion vessel
1. Drain the product. ( Page 36)
2. Measure the pre-charge pressure of the expansion ves-
sel at the vessel valve.
Condition: Pre-charge pressure < 0.075 MPa (0.75 bar)
Top up the expansion vessel in accordance with the
static height of the heating installation, ideally with ni-
trogen, otherwise with air. Ensure that the drain valve is
open when topping up.
3. If water escapes from the valve of the expansion
vessel, you must replace the expansion vessel
( Page 38).
4. Fill and purge the heating installation. ( Page 28)
12.14 Completing inspection and maintenance
work
1. Check the gas connection pressure (gas flow pressure).
( Page 29)
2. Check the CO content. ( Page 30)
3. Set the maintenance interval.
4. Check the product for tightness. ( Page 31)
5. Install the front casing. ( Page 18)
6. Fill out the relevant Service Record section in the
Benchmark Checklist located at the rear of this
document.
13 Troubleshooting
13.1 Eliminating faults
If fault messages (F.xx) appear, eliminate the fault after
referring to the table in the appendix or using the check
programmes. ( Page 26)
Overview of fault codes ( Page 46)
If several faults occur at the same time, the display shows
the corresponding fault messages for two seconds each in
alternation.
Press (max. three times) to restart the product.
If you are unable to eliminate the fault and the fault re-
curs despite reset attempts, contact customer service.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ecoFIT pure Series and is the answer not in the manual?

Vaillant ecoFIT pure Series Specifications

General IconGeneral
MountingWall-mounted
Efficiency RatingA
Fuel TypeNatural Gas
Warranty2 years
ModelecoFIT pure
Dimensions700mm x 390mm x 295mm
Efficiency94%

Related product manuals