Installer_manual_OEM_Vaillant_PROTO_3_GB-06/11-Vaillant
- 10 -
i
This technical data is valid for a new appliance with its
own heat exchangers.
Min.operatingoutsidetemperature(inheating) °C -20 -20 -20 -20 -20
Max.operatingoutsidetemperature(inheating) °C 30 30 30 30 30
(ow:45°C,return:40°C,outsidedrytemperature(wet)7(6)°C)
Heatingoutput kW 3.9 5.8 7.4 12.9 14
Powerinput kW 1.2 1.9 2.32 4.2 4.4
Ratedelectricalcurrent A 5.3 8.3 10 18.5 19
COP**A7(6)W45-40 3.2 3.06 3.18 3.03 3.21
(ow:35°C,return:30°C,outsidedrytemperature(wet):7(6)°C)
Heatingoutput kW 4.1 5.8 7.2 11.9 14.5
Powerinput kW 1 1.37 1.82 3.01 3.6
Ratedelectricalcurrent A 4.3 6 8 13 15.6
Typeofrefrigerant
Quantityofrefrigerant kg 1.195 1.13 1.81 2.485 3.385
Typeofcompressor Rotary
Typeofoil Polyolester
Typeofregulator Electronic
Fanspeed rpm 1000 1000 1000 805 1050
Maximumoperatingpressure(PS)
bar 45 45 45 45 45
Pa 45x10
5
45x10
5
45x10
5
45x10
5
45x10
5
Max.supplypressure.
bar 3 3 3 3 3
Pa 3x10
5
3x10
5
3x10
5
3x10
5
3x10
5
Nominalstaticpressure
bar 0.47 0.43 0.4 0.45 0.3
Pa 47x10
3
43x10
3
40x10
3
45x10
3
30x10
3
Nominalwaterowrateinheatingmode l/h 700 1000 1200 2100 2500
Flowratedetectionthreshold l/h 500 500 500 500 500
Min.volumeoftheinstallation l 14 21 28 42 49
Maxvolumeofheatpumpcircuit,without
auxiliarytank,forawateroutlettemperatureof
35°C
l 65 65 65 65 65
Minimumowtemperaturesetting(inheating) °C 20 20 20 20 20
Maximumowtemperaturesetting(inheating) °C 60 60 60 60 60
Heatpumpwatervolume l 1 1 1.2 2.3 2.3
TECHNICALDATA