Thermo plus 160/230/300/350 5 Troubleshooting
Error in the water system
Circulating pump does not operate (Aquavent 6000S and
Aquavent 6000SC only).
Error mode activated
In case of malfunctions the motor is switched off via the
error mode.
Reactivation of the circulating pump motor
For this purpose disconnect the power supply for > 2 min
(Observe 5.2 !).
After the power supply is reconnected the motor
performs a soft start.
The heater operation stops because the connected heat
exchangers (e.g. front box and side wall heater) provide
insufficient heat.
Flow rate too small, because
Air in the heater, heat exchanger or in system
sections
Taps/valves (flow controllers) throttled,
contaminated, closed
Contaminations in the system, e.g. filters or at bottlenecks
Circulating pump delivery rate insufficient
(air in pump housing)
Insufficient frost protection
System resistance too high (especially high in the cold)
Circulating pump defective
Adapter wiring harness “Valeo“ for variants > 85°C
defective
Heat exchanger provides not enough heat, because
Air in the heat exchangers and/or system sections
Contaminated heat exchanger surfaces (outside)
Insufficient air entry or air exit
Fan: Insufficient delivery rate /
incorrect direction of rotation / resistance too high
Antifreeze content too high
Approximate flow rate determination:
Heat flow [kW] according to type plate
Flow rate in [l/h] = x 860
Temperature difference t in [K] or [°C]
measured on the heater between water inlet and water outlet
Table 501 General error symptoms
Error symptom Possible cause