18 PP500 Installation Guide
ENG
SiPass Integrated ADD5100 connections
This is how to connect to a ADD5100 Dual Reader
Interface. The Wiegand interface is used. Note
that the PP500 must be set to the A2 Preset con-
guration (Wiegand).
ADD5100 Signal PP500
+12V V+ 1 V+
0V 0V 2 0V
D0 Data 0 4 D (D0)
D1 Data 1 5 D1
RED Red LED 8 RED
GRN Green LED 9 GREEN