8
The drain line from the temperature and pressure relief valve must
not be concealed or blocked and must be protected from freezing.
No valve of any kind should be installed between the temperature and
pressure relief valve and tank or in the drain line.
WARNING: IF THE WATER SUPPLY IS FROM A WELL, OR
KNOWN TO HAVE HARD WATER, IT IS RECOMMENDED TO USE
A PRESSURE RELIEF VALVE IN THE COLD-WATER LINE AS
WELL AS A T&P VALVE IN THE HOT WATER LINE.
E. WATER SUPPLY CONNECTIONS
WARNING: Some local codes mandate the use of a backflow
preventer or check valve or pressure-reducing valve. An
adequate expansion tank (or other adequate means) must be
installed to prevent pressure build up or damage from thermal
expansion when a check valve or backflow preventer or
pressure-reducing valve is used. Failure to do so could result in
tank leakage and therefore void the warranty. (See
INSTALLATION DIAGRAM 1 on page 20 and INSTALLATION
DIAGRAM 2 on page 20).
All water supply fittings on this heater are brass do not over tighten
or strip threads.
Provide a shut off valve in the cold-water line. Mark for future emergency
use.
It is recommended to use unions as shown in INSTALLATION
DIAGRAM 1 on page 20 and INSTALLATION DIAGRAM 2 on page
20.
Do not apply heat directly to the inlet or outlet as it includes a
plastic dip tube and O-rings which can melt.
Water connections are 3/4" male threaded fittings. Exception: They
are 1.5" male on the FD models.
F. BOILER SUPPLY CONNECTIONS
WARNING: Heat exchanger fluid must be non-toxic.
WARNING: Boiler temperature must be controlled by the boiler
hi limit not to exceed 200°F. Failure to do so will create a
hazardous installation and void the warranty.
All fittings on this heater are brass do not strip or cross threads.
It is recommended to use unions as shown in INSTALLATION
DIAGRAM 1 on page 20 and INSTALLATION DIAGRAM 2 on page
20.
Heat exchanger connections are 3/4" male threaded fittings.
Exception: They are 1" male on the FD models.
Connect the supply line (from the boiler) to the HX In” (heat
exchanger in) fitting of the heat exchanger.