Veeder-Root TLS-3 Series - Dual-Float Discriminating Sensor Alarms

Veeder-Root TLS-3 Series
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 19
Dual-Float Discriminating Sensor Alarms
MMM DD, YYYY HH:MM XM
L1: HIGH LIQUID ALARM
MMM DD, YYYY HH:MM XM
L1: FUEL ALARM
(Flashing Red light)
(Flashing Yellow light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
L1: SENSOR OUT ALARM
MMM DD, YYYY HH:MM XM
L1: LIQUID ALARM
(Flashing Yellow light)
(Flashing Yellow light)
MMM DD, YYYY HH:MM XM
L1: SHORT ALARM
ALARM
TEST
ALARM
TEST
CAUSE:
The sensor at the location shown has
detected fuel vapor or liquid.
ACTION:
Investigate the cause of the alarm and
take appropriate action.
CAUSE:
The sensor at the location shown has
detected at least 8 inches (20.3 cm) of
non-hydrocarbon liquid.
ACTION:
Call for service following the procedures
established for your site.
CAUSE:
The sensor at the location shown has
detected at least 1 inch (25 mm) of
non-hydrocarbon liquid.
ACTION:
Call for service following the proce-
dures established for your site.
CAUSE:
The sensor at the location shown has
been disconnected or is inoperative.
ACTION:
Call for service following the proce-
dures established for your site.