Page 32
Wireless Pressurized Line Leak Detection Tests (WPLLD Option)
TO START A WPLLD TEST
In the Operating mode, press Function until the display reads:
Press Step and the display reads:
Press Step to accept all lines. To select a single line, press Change until
you see the line you want, then press Enter and Step. The display reads:
This step lets you select a 3.0, 0.2, or 0.1 gph (0.38, 0.76, 11.3 lph) line
leak test to run on the selected line(s). If your console does not have 0.2 or
0.1 gph test options, you will not see these selections.
START LINE PRESSURE TEST
PRESS <STEP> TO CONTINUE
To select a 3.0 gph test, press Step, or press Change to select a
0.2 or 0.1 gph test, then press Enter.
To select a 3.0 gph test, press Step. The display reads:
To run the selected test, press Step. The system displays the mes-
sage (in this example for all lines):
Press Enter to begin the test. The display reads:
To exit this function, press Step.
3.0 GPH
PRESS <STEP> TO CONTINUE
START LINE TEST: ALL LINE
PRESS <ENTER>
W#: TEST PENDING
PRESS <STEP> TO CONTINUE
NOTE: WPLLD is available with UL approved consoles only.