TO START A PLLD TEST
In the Operating mode, press Function until the display reads:
Press Step and the display reads:
Press Step to accept all lines. To select a single line, press Change until
you see the line you want, then press Enter and Step. The display below
appears:
This step lets you select a 3.0, 0.2, or 0.1 gph (0.38, 0.76, 11.3 lph) line
leak test to run on the selected line(s). If your console does not have 0.2 or
0.1 gph test options, you will not see these selections.
SELECT LINE
ALL LINES
SELECT TEST TYPE
3.0 GPH
To select a 3.0 gph test, press Step, or press Change to select a
0.2 or 0.1 gph test, then press Enter.
To select a 3.0 gph test, press Step. The display reads:
To run the selected test, press Step. The system displays the mes-
sage (in this example for all lines):
Press Enter to begin the test. The system displays:
To exit this function, press Step.
3.0 GPH
PRESS <STEP> TO CONTINUE
START LINE TEST: ALL LINE
PRESS <ENTER>
Q#: RUNNING PUMP
PRESS <STEP> TO CONTINUE
Pressurized Line Leak Detection Tests (PLLD Option)