PLLD/WPLLD Line Leak Detection Alarms
MMM DD, YYYY HH:MM XM
Q1: GROSS LINE FAIL
(Flashing Red light)
MMM DD, YYYY HH:MM XM
W1: GROSS LINE FAIL
MMM DD, YYYY HH:MM XM
Q1: PERIOD LINE FAIL
MMM DD, YYYY HH:MM XM
W1: PERIOD LINE FAIL
(Flashing Red light)
ALARM
TEST
ALARM
TEST
MMM DD, YYYY HH:MM XM
Q1: ANNUAL LINE FAIL
MMM DD, YYYY HH:MM XM
W1: ANNUAL LINE FAIL
(Flashing Red light)
(Flashing Red light)
MMM DD, YYYY HH:MM XM
Q1: SHUTDOWN ALARM
MMM DD, YYYY HH:MM XM
W1: SHUTDOWN ALARM
ALARM
TEST
ALARM
TEST
CAUS E:
3 gph (11.3 lph) line test failure. Dis-
pensing halts, if programmed to do so,
while the alarm is active.
ACTION:
Consult W/PLLD Alarm Quick Help
Guide and Pressure Line Leak Diag
(Diagnostic Mode).
CAUSE:
0.2 gph (0.76 lph) test failure. Dispens-
ing halts, if programmed to do so.
ACTION:
Consult W/PLLD Alarm Quick Help
Guide and Pressure Line Leak Diag
(Diagnostic Mode).
CAUS E:
0.1 gph (0.38 lph) test failure. Dis-
pensing halts, if programmed to do
so.
ACTION:
Consult W/PLLD Alarm Quick
Help Guide and Pressure Line
Leak Diag (Diagnostic Mode).
CAUSE:
System shut down line because of
failed line leak test, or an alarm
assigned to disable the line is active.
ACTION:
Identify offending alarm, and see the
Troubleshooting section in manual no.
576013-610 for corrective action.