Connecting Probe/Sensor Wiring to Consoles TLS-350/ProMax/EMC Consoles
61
3 PROBE/3 SENSOR INTERFACE MODULE - I.S. BAY
Figure 59. 3 Probe / 3 Sensor Interface Module Wiring
Connecting Devices
Connect Mag Probes and sensors in the table below to the appropriate terminals (Probe or Sensor) on the Probe/
Liquid Sensor Interface module as shown in Figure 60.
Device Wires Observe Polarity
Mag Probe 2 Yes
Interstitial sensor for fiberglass/steel tanks 2 No
Sump sensor 2 No
Discriminating dispenser pan sensor 2 No
Discriminating containment sump sensor 2 No
Hydrostatic sensor (for all double-wall tanks) 2 No
PROBE / LIQUID SENSOR INTERFACE MODULE
MAXIMUM PROBE
OUTPUT RATINGS:
13 VDC
0.2 AMP
123123
PROBE SENSOR
consoles\3pbsn.eps
Console
+
Probe
#1
Sensor
#1
Up to 3
Probes
Up to 3
Sensors
+ + +
Rigid Conduit
(enters Console
through an I.S. Bay
knockout)
Attach Cable Shields to Ground
Lug Closest to Conduit Entry