Connecting Probe/Sensor Wiring to Consoles TLS-350/ProMax/EMC Consoles
64
TYPE A INTERFACE MODULE - I.S. BAY
Figure 62. Type A Interface Module
Connecting Devices
Connect sensors in the table below to the appropriate terminals on the Type A Interface module as shown in
Figure 62.
Device Wires Observe Polarity
4SITE discriminating Interstitial sensor for
fiberglass tanks
2Yes
Micro sensor 2 Yes
Solid-state dispenser pan sensor 2 Yes
Solid-state containment sump sensor 2 Yes
SENSOR
MAXIMUM SENSOR
OUTPUT RATINGS:
13 VDC
.20 AMP
+ + + + + + + +
1 2 3 4 5 6 7 8
TYPE A INTERFACE MODULE
consoles\taimw.eps
Console
Up to 8
Sensors
Sensor
#1
Sensor
#2
Sensor
#8
Attach Cable Shields to Ground
Lug Closest to Conduit Entry
++ +
Rigid Conduit
(enters Console
through an I.S. Bay
knockout)