ISD Alarm Message Diagnostics DEGRD COLLECT
12
DEGRD COLLECT
A 7-day Degradation A/L Test failure occurs when the A/L ratio is at least 25% below the lower certified A/L ratio
or at least 25% above the upper certified ratio.
ISD MONITORING CATEGORY
Vapor Collection Monitoring for sites equipped with assist vapor recovery systems is responsible for ensuring that
proper front-end vapor capture is occurring during fueling events. Among other components, front-end equipment
includes the nozzle, hose and the breakaway. Vapor collection is assisted by vacuum motor(s) located inside the
dispenser vapor return piping.
DIAGNOSTIC PROCEDURE
Perform the TP 201.5 A/L test. To find the hose that triggered the alarm by looking at the Collection Tests in the
ISD Daily Report in the normal menu.
Refer to the Clear Test Repair Menu (on page 36) for clearing this alarm on the TLS after repairs are complete.
FIELD NOTES
This alarm should not occur at a VST Balance site. If it does check EVR Type setup in ISD.

Table of Contents

Other manuals for Veeder-Root TLS-350 PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-350 PLUS and is the answer not in the manual?

Veeder-Root TLS-350 PLUS Specifications

General IconGeneral
CategoryMeasuring Instruments
Number of Tanks SupportedUp to 16
Water DetectionYes
Inventory ManagementYes
Delivery ReportingYes
Alarm ManagementYes
DisplayLCD
EnclosureNEMA 4X
ModelTLS-350 PLUS
ManufacturerVeeder-Root
Temperature MeasurementYes
TypeAutomatic Tank Gauge
Leak DetectionYes
CommunicationRS-232, Ethernet
Product TypeTank Gauging System
ComplianceUL, ATEX

Related product manuals