ISD Reports Viewing ISD Reports via RS-232 Connection
43
BALANCE DAILY DETAIL STATUS CODES
Question
When and why do the status codes appear? (see example below.)
Explanation
Balance Systems - Hose W,F,G,N Results
Next to each hose collection daily average A/L result there is an assessment. The absence of any of the results
listed above indicates a pass. If any of the listed conditions W,G or F exist, they will post before a pass. The
assessment can indicate the result for one of two tests called Statistical Test or Flow Performance Test.
W - Warning for Statistical (BLKD).
- Indicates a statistical warning if BLKD appears instead of the A/L value.
- Indicates a Flow Collect warning if the A/L value appears next to it.
- Warning for Flow Performance Test and will appear with A/L value.
- A Flow Collect warning will convert to a failure and shutdown on the 2nd day.
F - Statistical Failure - A BLKD is posted instead of an A/L value.
- Automobiles equipped with ORVR equipment appear as a blocked dispensing event (A/L very low). ISD
separates out this type of activity from blockages that are caused by something other than ORVR vehicles. It
does this statistically using multiple dispensing events. When there are more blockages than would be
expected from normal ORVR traffic, a BLKD warning is issued.
G - Failure for Flow Performance Test and will appear with A/L value.
N - No Test.

Table of Contents

Other manuals for Veeder-Root TLS-350 PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-350 PLUS and is the answer not in the manual?

Veeder-Root TLS-350 PLUS Specifications

General IconGeneral
CategoryMeasuring Instruments
Number of Tanks SupportedUp to 16
Water DetectionYes
Inventory ManagementYes
Delivery ReportingYes
Alarm ManagementYes
DisplayLCD
EnclosureNEMA 4X
ModelTLS-350 PLUS
ManufacturerVeeder-Root
Temperature MeasurementYes
TypeAutomatic Tank Gauge
Leak DetectionYes
CommunicationRS-232, Ethernet
Product TypeTank Gauging System
ComplianceUL, ATEX

Related product manuals