11 Diagnostics and servicing
VEGAMET 341 • 4 … 20 mA
63730-EN-210616
incorrect parameter adjustment, a fault signal is triggered. In case of
an instrument defect or line break/shortcircuit, a fault signal is also
triggered.
The fault indication lights up in case of failure and the current output
aswellastherelaysreactaccordingtotheconguredfaultmode.If
thefailsaferelaywascongured,itwilldeenergize.Inaddition,one
of the following error messages is outputted on the display and the
background lighting changes to colour acc. to NAMUR NE 107 (e.g.
red in case of a fault, orange in case of a function check).
Error code Cause Rectication
F003
Hardware: CRC
error
CRC error (error
with self-check)
Switchtheinstrumento/on
Carry out a reset
Send instrument for repair
F012
Sensor input:
Hardware error
Hardware error,
sensor input
Switchtheinstrumentoandon
Send instrument for repair
F013
Sensor input:
Sensor error
The input of the
measuring point
returns an error
The connected
sensor returns
an error
Switchdevice/sensoroanon
Send device/sensor for repair
F014
Sensor input:
Short-circuit
Sensor cur-
rent > 21 mA or
short-circuit
Check sensor, e.g. on failure
Remove short-circuit
F015
Sensor input:
Line break
Sensor in boot
phase
Sensor current
< 3.6 mA or line
break
Check sensor, e.g. on failure
Remove line break
Check connection of the sensor
F034
EEPROM: CRC
error
EEPROM: CRC
error
Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
F035
ROM: CRC error
ROM: CRC error Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
F036
No operable
software
No executable
program
Software update
failed
Carry out another software update
Send instrument for repair
F037
RAM
RAM defective Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
F040
General hard-
ware error
Hardware error Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
Failure