Command Description
$ Measured value enquiry with 11 places as oating point and
with unit
Note:
With the switching inputs of PLICSRADIO
®
C62 (measure-
ment loops 4 6) the value 0 (switch open) and 100 (switch
closed) are transmitted as measured values, the units are
deleted.
The above commands of the measured value enquiry can be
also combined with the following options:
Option Description
TIME The current date/time is added to the answer
REPEAT x The measured value is sent automatically by the signal
conditioning instrument every x seconds
STORE The enquiry is saved up to the STORE option and executed
after a restart (only available with RS232 interface)
SUM A check sum is transmitted for each line which is sent
Information:
For commands and options no dierence is made between
small and capital letters. Each character string is terminated
with Carriage Return CR = CHR (13). The individual
commands and options are described below more in detail.
2.3 Version enquiry with command VERSION
With the command VERSION, the current protocol version can
be determined.
Example
l Enquiry: version
l Answer: VEGA ASCII Version 1.00
2.4 Help with command HELP
With the command HELP, a short information can be retrieved.
Options
12 Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO
VEGA ASCII protocol
30768-EN-070730