2.5 Delete the settings with the command
CLEARSTORE
With the command CLEARSTORE, the settings of the option
STORE are deleted in the EEPROM and the automatic
repetition of the measured values is stopped.
2.6 Measured value enquiry with command %
2.6.1 % individual enquiry
As answer on the individual enquiry, the PC/DCS value stated
in the enquiry is delivered. The measured value is transmitted
with three positions in front of the decimal point and one
position after the decimal point without unit.
Number of bytes Sign
Identier 1 %
Begin 1 3 001 030 or 1 30
End identication 1 CR
l Identier: "%" (1 character)
l Start: No. of the requested PC/DCS output (1 3 signs)
l End identication: Carriage Return CR (1 sign)
Total length of the telegram: 3 5 signs
Number of bytes Sign
T1 1 =
DCS no. 3 001 030
T2 1 #
Value 5 6 -067.3
T3 1 %
End identication 1 CR
l T1: "=" (1 sign)
l DCS no.: No. of the PC/DCS output as 3-digit decimal
number
l T2: "#" (1 character)
l Value: Numerical value of the PC/DCS output or with
interferred measured value the text "FAULT"
Formatting of the value:
Enquiry of the control system
Answer from the signal con-
ditioning instrument
Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO 13
VEGA ASCII protocol
30768-EN-070730