Number of bytes Sign
Value 7 -000673
T3 1 #
Unit 0 n xxx
End identication 1 CR
l T1: "=" (1 sign)
l DCS no.: No. of the PC/DCS output as 3-digit decimal
number
l T2: "#" (1 character)
l Value: Numerical value of the PC/DCS output or in case of
faulty measured value the text "FAULT"
Formatting of the value:
Sign Meaning
1
"- ": Minus with negative numbers
" ": Space with positive numbers
2 7 6-digit number after the decimal point
l T3: "#" (1 character)
l Unit: Unit as text (0 n unit)
l End identication: Carriage Return CR (1 sign)
Total length of the telegram: (End-Start+1)*(14 signs+Unit
sign)
Enquiry:
?001-003
Answer:
=001# 000673#%
=002# 00824#kg
=003#-000673#m
2.9 Measured value enquiry with command $
2.9.1 $ individual enquiry
As answer to the individual enquiry, the PC/DCS value stated
in the enquiry is delivered. The measured value is transmitted
with 11 decimal places as oating point and with unit.
Example:
Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO 29
VEGA ASCII protocol
30768-EN-070730