l T3: "#" (1 character)
l Unit: Unit as text (0 n unit)
l End identication: Carriage Return CR (1 sign)
Total length of the telegram: Quantity*(14 characters+Unit
character)
Enquiry:
?001L003
Answer:
=001# 000673#%
=002# 008246#kg
=003#-000673#m
2.8.1 ? Block enquiry with range
As an answer to the range enquiry, the range stated in the
enquiry with PC/DCS values is delivered. The measured value
is transmitted with six decimal places without decimal point
and with unit.
Number of bytes Sign
Identier 1 ?
Begin 1 3 001 030 or 1 30
Separator 1 -
End 1 3 001 030 or 1 30
End identication 1 CR
l Identier: "?" (1 character)
l Start: Start no. of the requested PC/DCS output (1 3
characters)
l Separator: "-" (1 sign)
l End: End no. of the requested PC/DCS output (1 3
signs)
l End identication: Carriage Return CR (1 sign)
Total length of the telegram: 5 9 characters
(End-Start+1)-times repetition of the following telegram
Number of bytes Sign
T1 1 =
DCS no. 3 001 030
T2 1 #
Example:
Enquiry of the control system
Answer from the signal con-
ditioning instrument
28 Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO
VEGA ASCII protocol