always sorted according to PC/DCS output number. The
following chart shows the addressing of the temporary memory
via Modbus. The values are accessed via FC 3 and 4. The
status information is also transmitted as float value. 8 byte are
needed for one output, corresponding to 4 registers.
Information:
Note: A float value comprises 2 registers, i.e. a total of 4 bytes!
Register address in
Modicon
Temporary memory of VEGAMET/PLICSRA-
DIO (2 words = 4 byte)
31001 PC/DCS output 1: Measured value
31003 PC/DCS output 1: Status
31005 PC/DCS output 2: Measured value
31007 PC/DCS output 2: Status
31009 PC/DCS output 3: Measured value
31011 PC/DCS output 3: Status
31013 PC/DCS output 4: Measured value
31015 PC/DCS output 4: Status
31017 PC/DCS output 5: Measured value
31019 PC/DCS output 5: Status
31021 PC/DCS output 6: Measured value
31023 PC/DCS output 6: Status
Register address in
Modicon
Temporary memory of VEGASCAN (2 words =
4 byte)
31001 PC/DCS output 1: Measured value
31003 PC/DCS output 1: Status
31005 PC/DCS output 2: Measured value
31007 PC/DCS output 2: Status
31009 PC/DCS output 3: Measured value
31011 PC/DCS output 3: Status
31013 PC/DCS output 4: Measured value
31015 PC/DCS output 4: Status
31017 PC/DCS output 5: Measured value
31019 PC/DCS output 5: Status
31021 PC/DCS output 6: Measured value
Modbus-TCP, VEGA ASCII protocol - VEGAMET 624/625, VEGASCAN 693, PLICSRADIO 7
Function as Modbus-TCP server
30768-EN-070730