EasyManua.ls Logo

Vega VEGAMET 624 - Page 32

Vega VEGAMET 624
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note:
To contact the instrument, a corresponding IP address must be
available in the instrument. Each instrument is preset to address
192.168.200.200. Enter the address and subnet mask corresponding
to your network directly via the keyboard. As an alternative, addressing
is also possible via DHCP and a host name. Briey interrupt the
operating voltage after each modication, then the instrument is
accessible via its IP address or host name everywhere in the network.
In addition, these specications must be entered in the DTM (see
chapter "Parameter adjustment with PACTware").
2
3
1
Fig. 7: Connection of the PC via Ethernet
1 Ethernet interface of the PC
2 Ethernet connection cable (Cross-Over cable)
3 Ethernet interface
The RS232 interface is particularly suitable for easy modem
connection. External analog, ISDN and GSM modems with standard
interface can be used. T he necessary RS232 modem connection
cable is included with the delivery. To reduce EMC interference, you
should mount the supplied ferrite bead on the RS232 modem
connection cable. Via a visualisation software, measured values can
be retrieved remotely and further processed. Alternatively, the
autonomous time or event controlled transmission of measured values
via e-mail is also possible. Remote parameter adjustment of the
instrument and the connected sensors is also possible with
PACTware.
Connection of the mo-
dem via RS232
32 VEGAMET 624 4 20 mA/HART signal conditioning instrument
7 Setup with PACTware
28969-EN-091116

Other manuals for Vega VEGAMET 624