? E030
l Sensor in boot phase
l value not valid
à Check sensor parameter adjustment
? E034
l EEPROM defective
à Carry out a reset
à Send instrument for repair
? E035
l EEPROM CRC error
à Carry out a reset
à Send instrument for repair
? E036
l Instrument software not executable (during software update or
after failed update)
à Wait until software update is nished
à Carry out another software update
? E053
l Sensor measuring range not read correctly
à HART communication error: Check sensor cable and
screening
? E062
l Pulse priority too small
à Increase under "Output" the entry "Pulse output all" so that
max. one pulse per second is outputted.
? E110
l Relay switching points too close together
à Increase the dierence between the two relay switching points
? E111
l Relay switching points interchanged
à Change relay switching points for "On/O"