SI23 Solar Pump VFD Manual
21
E.SC
System
abnormal
●Deceleration is too short
●Short circuit of solar drive
output or phase output short
circuit to ground
●Module damage
●EMC interface
●Prolong acceleration time
●To check peripheral equipment
●Ask to support
Check the wiring layout, cable
ground
E.oH1
VFD over-heat
●Temperature is too high
●Air channel is blocked
Fan connection parts is
loose
●Fan is damaged
●Temperature detection
circuit fault
Make the environment meet the
requirement
●Clear the air channel
Check and reconnect the wire
●Change the same new fan
●Seek support from factory
E.oH2
Rectifier
over-heat
●Temperature is too high
Air channel is blocked
●Fan connection parts is
loose
Fan is damaged
Temperature detection
circuit fault
●Make the environment meeting the
requirement
Clear the air channel
Check and reconnect the wire
Change the same new fan
Seek support from factory
E.TE1
Motor static
detection fault
Detection overtime
●Start static detection while
motor is running
Capacitance difference is
too big between motor and
VFD
Motor parameter setting
mistake
Check motor connection wire
Detect after motor stopping totally
Change VFD model
Reset parameter according to
nameplate
E.TE2
Motor rotation
detection fault
●Detect while motor is
running
Detect with load
Detection overtime
●Capacitance difference is
too big between motor and
VFD
●Motor parameter setting
mistake
Detect after motor stop totally
Re-detect without load
Check motor connection wire
Change VFD model
Reset parameter according to
nameplate
E.EEP
Memory fault
●Electromagnetic disturb in
memory period
EEPROM damage
Resume load and save
Seek support from factory
LiFE
Reserved