SI23 Solar Pump VFD Manual
41
F21.49(0x5531)
Sudden voltage
increase threshold
0.0%20.0%
5.0%
F21.50(0x5532)
Reserved
F21.51(0x5533)
Reserved
F21.52(0x5534)
Reserved
F21.53(0x5535)
Functional selection
LED0: Inermittent Operation Storage
0:None; 1:Storaged
LED00:Stop Mode When Alarm
0:Slow down
1:Free stop
LED000:Reserved
LED0000:Reserved
0000
F21.54(0x5536)
Times of Inermittent
Operation
01000
0
F21.55(0x5537)
Start time of
Inermittent Operation
0min3000min
0
F21.56(0x5538)
Stop time of
Inermittent Operation
0min3000min
0
F21.57(0x5539)
Pump Clean
Frequency
0.00Hz300.00Hz
25.00Hz
F21.58(0x553A)
FWD Running Time
0s3000s
30s
F21.59(0x553B)
REV Running Time
0s3000s
30s
F21.60(0x553C)
Cycle Times
060
5
F21.61(0x553D)
Power Limitation
0.01000.0
0.0
F21.62(0x553E)
Power Limitation Kp
0.0100.0
1.0
F21.63(0x553F)
Power Limitation Ki
0.0100.0
1.0
● Photovoltaic Pump Special Monitor Parameters
Function code
Function name
Setting range
and definition
Default setting
C04.00(0x2500)
Frequency reference
0.01Hz
Read only
C04.01(0x2501)
Output frequency
0.01Hz
Read only
C04.02(0x2502)
Output current
0.1A
Read only
C04.03(0x2503)
Cycle Times 1
Read only
C04.04(0x2504)
Cycle Times 2
Read only
C04.05(0x2505)
Reserved
Read only
C04.06(0x2506)
Operation Time
1min
Read only
C04.07(0x2507)
Stop Time
1min
Read only
C04.08(0x2508)
Reserved
Read only
C04.09(0x2509)
Reserved
Read only

Related product manuals