SI23 Solar Pump VFD Manual
25
F01.02(0x0102)
Frequency
reference source
channel A
V/F SVC FVC
The frequency converter sets the given source of
the frequency.
0: Keyboard digital given frequency
1: Keyboard analog potentiometer given
2: Current/voltage analog AI given
3: Reserved
4: Reserved
5: Terminal pulse PUL given
6: RS485 communication given
7: Terminal UP/DW control
8: PID control given
9: Program Control (PLC) given
10: Option card
11: Multi-speed speed given
0
(011)
F01.09(0x0109)
Keyboard digital
given frequency
V/F SVC FVC
Used to set and modify the keyboard digital setting
frequency.
50.00Hz
(0.00Hzupper
limit frequency
setting)
F01.10(0x010A)
Maximum
frequency
V/F SVC FVC
The maximum frequency that the frequency
converter can set.
50.00Hz
(upper limit
frequency
600.00Hz)
F01.12(0x010C)
Upper limit
frequency digital
setting
V/F SVC FVC
The upper line frequency is given when F01.11 is
set to 0.
0.00Hz
(0.00Hzupper
limit frequency
digital setting)
F01.13(0x010D)
Lower limit
frequency
V/F SVC FVC
Given a lower frequency limit, the given frequency
is limited.
0.00Hz
(0.00Hzupper
limit frequency
digital setting)
F01.22(0x0116)
Acceleration
time 1
V/F SVC FVC
The time required for the output frequency to
accelerate from 0.00 Hz to the time reference
frequency.
1s65000s(F01.21 = 0)
0.1s6500.0s(F01.21 = 1)
0.01s650.00s(F01.21 = 2)
Model setting
(0.01s
650.00s)
F01.23(0x0117)
Deceleration
time 1
V/F SVC FVC
The time it takes for the output frequency to
decelerate from the time reference frequency to
0.00 Hz.
Model setting
(0.01s
650.00s)