SI23 Solar Pump VFD Manual
25
Frequency
reference source
channel A
V/F SVC FVC
The frequency converter sets the given source of
the frequency.
0: Keyboard digital given frequency
1: Keyboard analog potentiometer given
2: Current/voltage analog AI given
3: Reserved
4: Reserved
5: Terminal pulse PUL given
6: RS485 communication given
7: Terminal UP/DW control
8: PID control given
9: Program Control (PLC) given
10: Option card
11: Multi-speed speed given
Keyboard digital
given frequency
V/F SVC FVC
Used to set and modify the keyboard digital setting
frequency.
50.00Hz
(0.00Hz~upper
limit frequency
setting)
V/F SVC FVC
The maximum frequency that the frequency
converter can set.
50.00Hz
(upper limit
frequency~
600.00Hz)
Upper limit
frequency digital
setting
V/F SVC FVC
The upper line frequency is given when F01.11 is
set to 0.
0.00Hz
(0.00Hz~upper
limit frequency
digital setting)
V/F SVC FVC
Given a lower frequency limit, the given frequency
is limited.
0.00Hz
(0.00Hz~upper
limit frequency
digital setting)
V/F SVC FVC
The time required for the output frequency to
accelerate from 0.00 Hz to the time reference
frequency.
1s~65000s(F01.21 = 0)
0.1s~6500.0s(F01.21 = 1)
0.01s~650.00s(F01.21 = 2)
Model setting
(0.01s~
650.00s)
V/F SVC FVC
The time it takes for the output frequency to
decelerate from the time reference frequency to
0.00 Hz.
Model setting
(0.01s~
650.00s)