DEFAULT VALUES
Parameter min max step default
winter manual
setpoint
2.0°C 35.0°C 0.1°C 21.0°C
summer manual
setpoint
2.0°C 35.0°C 0.1°C 25.0°C
T1 winter 2.0°C T2 0.1°C 15.0°C
T2 winter T1 T3 0.1°C 18.0°C
T3 winter T2 35.0°C 0.1°C 21.0°C
T2 summer 10.0°C T3 0.1°C 23.0°C
T3 summer T2 35.0°C 0.1°C 25.0°C
antifreeze temperature 1.0°C 10.0°C 0.1°C 6.0°C
operating mode winter summer - winter
regulation type ON/OFF PROP - ON/OFF
ON/OFF hysteresis 0.1°C 1.0°C 0.1°C 0.3°C
proportional band 0.5°C 5.0°C 0.1°C 0.5°C
proportional period 10’ 30’ 10’ 10’
password 0 999 1
000
(deactivated)
winter hour meter 0 1 0
summer hour meter 0 1 0
summer hour meter,
enable
ON OFF - ON
winter/summer time
change
Summer: LAST
DAY7 March
02:00 AM
Winter: LAST
DAY7 October
3:00 AM
activation delay 0’ 45’ 15’ 0’
timed operations 0h 99d 1h 0h

Related product manuals