89
User Manual 10H52258UM60 - Rev. 3 - 01/2019
Specifications APM 400/600
11.4
Electrical Specifications (Input Rectifier)
Item Unit
Rated AC input voltage
1
Vac
wire (+PE) TN/TT/IT power
distribution system
2
2
Power factor
load, (half load)
0.99 (0.98)
3
distortion
5
% 3
1. Rectifiers will operate at any of the rated supply voltages and frequencies without further adjustment.
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging the
battery.
3. IEC62040-3: at rated load, input voltage is 400V, battery remains fully charged.
4. With input voltage at nominal value and voltage distortion THD
V
≤1%.
5. Measured with an input THDv < 1%
11.5
Electrical Specifications (Intermediate DC Circuit)
Item Unit
Rated battery bus voltage
(nominal)
Block 38~ 44 (12 Vdc)
Float voltage
(VRLA)
2.25 (selectable from 2.2
Constant current and constant voltage charge mode
Boost voltage
(VRLA)
2.25 (selectable from 2.3 to 2.35)
Constant current and constant voltage charge mode
Boost control
boost current trigger 0.050C10 (selectable from 0.001 to
0.070)
Boost-float current trigger 0.010C10 (selectable from 0.001 to
0.025)
8hr safety time timeout (selectable from 8hr to 30hr)
Boost mode inhibit also selectable
EOD voltage
(VRLA)
1.67 (selectable from 1.60 to 1.90)