1. Press and hold the configuration button until the bottom LED in the left column starts flashing. This means you entered the
configuration mode, and you can change the scaling factor. As said, this parameter can be ignored in the case of VE.Bus
Multis.
2. Press the button to go to the next setting. The lower left LED will turn on, indicating that the generator current can be set.
3. Turn the knob until the display indicates 12.
4. Press the button to advance to the “Upper Shore limit for AC input 1” setting.
5. If you want the maximum shore current the operator can set to be lower than 32A, you can change this value.
6. Since the next 3 parameters (Upper Shore limit for AC input 2, 3 and 4) do not need to be configured, you can press the
button 4 times to step through the settings and finalise the configuration.
Digital Multi Control
Page 8 Configuration